Transverse Load Tables:

Axial Load Tables:

Racking Shear Capacity

Weight of Materials:

Transverse Load Tables



Printer Friendly Version

4 1/2" EMERCOR STRUCTURAL INSULATED PANEL (SIP)
Transverse Loading
(OSB/Drywall)

 

 

*For Roof Applications with 4 1/2" OSB/Drywall panel use L/360

Live Load
(psf)

Dead Load
(psf)

Maximum Allowable Deflection

L/180

L/240

L/360

L/480

20

10

7' - 08"

7' - 00"

6' - 01"

5' - 06"

20

15

7' - 08"

7' - 00"

6' - 01"

5' - 06"

20

20

7' - 03"

7' - 00"

6' - 01"

5' - 06"

40

10

5' - 10"

5' - 06"

4' - 10"

4' - 05"

40

15

5' - 03"

5' - 03"

4' - 10"

4' - 05"

40

20

4' - 10"

4' - 10"

4' - 10"

4' - 05"

50

10

4' - 10"

4' - 10"

4' - 06"

4' - 01"

50

15

4' - 06"

4' - 06"

4' - 06"

4' - 01"

50

20

4' - 02"

4' - 02"

4' - 02"

4' - 01"

100

10

2' - 08"

2' - 08"

2' - 08"

2' - 08"

100

15

2' - 06"

2' - 06"

2' - 06"

2' - 06"

100

20

2' - 05"

2' - 05"

2' - 05"

2' - 05"

  1. The panel deflection listed above is the instantaneous deflection due to live load. The dead load deflection can be calculated from the ratio of (DL/LL). The long-term deflection of dead load is about 2.5 times its instantaneous deflection in dry service conditions.
  2. The panels should be used in dry service conditions only.

back to top



Printer Friendly Version

4 1/2" EMERCOR STRUCTURAL INSULATED PANEL (SIP)
Transverse Loading
(OSB/OSB)

Live Load
(psf)

Dead Load
(psf)

Maximum Allowable Deflection

L/180

L/240

L/360

L/480

20

10

8' - 09"

8' - 00"

7' - 00"

6' - 04"

20

15

8' - 09"

8' - 00"

7' - 00"

6' - 04"

20

20

8' - 09"

8' - 00"

7' - 00"

6' - 04"

40

10

7' - 00"

6' - 04"

5' - 06"

5' - 00"

40

15

7' - 00"

6' - 04"

5' - 06"

5' - 00"

40

20

7' - 00"

6' - 04"

5' - 06"

5' - 00"

50

10

6' - 06"

5' - 11"

5' - 02"

4' - 08"

50

15

6' - 06"

5' - 11"

5' - 02"

4' - 08"

50

20

6' - 06"

5' - 11"

5' - 02"

4' - 08"

100

10

4' - 03"

4' - 03"

4' - 01"

3' - 09"

100

15

4' - 01"

4' - 01"

4' - 01"

3' - 09"

100

20

3' - 11"

3' - 11"

3' - 11"

3' - 09"

  1. The panel deflection listed above is the instantaneous deflection due to live load. The dead load deflection can be calculated from the ratio of (DL/LL). The long-term deflection of dead load is about 2.5 times its instantaneous deflection in dry service conditions.
  2. The panels should be used in dry service conditions only.

back to top



Printer Friendly Version

6 1/2" EMERCOR STRUCTURAL INSULATED PANEL (SIP)
Transverse Loading
(OSB/Drywall)

 

 

*For Roof Applications with 6 1/2" OSB/Drywall panel use L/360

Live Load
(psf)

Dead Load
(psf)

Maximum Allowable Deflection

L/180

L/240

L/360

L/480

20

10

9' - 08"

8' - 10"

7' - 08"

7' - 00"

20

15

9' - 08"

8' - 10"

7' - 08"

7' - 00"

20

20

9' - 08"

8' - 10"

7' - 08"

7' - 00"

40

10

7' - 08"

7' - 00"

6' - 01"

5' - 06"

40

15

7' - 02"

7' - 00"

6' - 01"

5' - 06"

40

20

6' - 07"

6' - 07"

6' - 01"

5' - 06"

50

10

6' - 07"

6' - 06"

5' - 08"

5' - 02"

50

15

6' - 01"

6' - 01"

5' - 08"

5' - 02"

50

20

5' - 08"

5' - 08"

5' - 08"

5' - 02"

100

10

3' - 07"

3' - 07"

3' - 07"

3' - 07"

100

15

3' - 05"

3' - 05"

3' - 05"

3' - 05"

100

20

3' - 03"

3' - 03"

3' - 03"

3' - 03"

  1. The panel deflection listed above is the instantaneous deflection due to live load. The dead load deflection can be calculated from the ratio of (DL/LL). The long-term deflection of dead load is about 2.5 times its instantaneous deflection in dry service conditions.
  2. The panels should be used in dry service conditions only.

back to top



Printer Friendly Version

6 1/2" EMERCOR STRUCTURAL INSULATED PANEL (SIP)
Transverse Loading
(OSB/OSB)

Live Load
(psf)

Dead Load
(psf)

Maximum Allowable Deflection

L/180

L/240

L/360

L/480

20

10

10' - 04"

9' - 05"

8' - 03"

7' - 06"

20

15

10' - 00"

9' - 05"

8' - 03"

7' - 06"

20

20

9' - 04"

9' - 04"

8' - 03"

7' - 06"

40

10

8' - 03"

7' - 06"

6' - 06"

5' - 11"

40

15

8' - 00"

7' - 06"

6' - 06"

5' - 11"

40

20

7' - 07"

7' - 06"

6' - 06"

5' - 11"

50

10

7' - 07"

6' - 11"

6' - 01"

5' - 06"

50

15

7' - 04"

6' - 11"

6' - 01"

5' - 06"

50

20

7' - 01"

6' - 11"

6' - 01"

5' - 06"

100

10

4' - 06"

4' - 06"

4' - 06"

4' - 04"

100

15

4' - 04"

4' - 04"

4' - 04"

4' - 04"

100

20

4' - 02"

4' - 02"

4' - 02"

4' - 02"

  1. The panel deflection listed above is the instantaneous deflection due to live load. The dead load deflection can be calculated from the ratio of (DL/LL). The long-term deflection of dead load is about 2.5 times its instantaneous deflection in dry service conditions.
  2. The panels should be used in dry service conditions only.

back to top



Axial Load Tables:



Printer Friendly Version

4 1/2" EMERCOR STRUCTURAL INSULATED PANEL (SIP)
Axial Loading (pounds/linear foot)
(OSB/Drywall)

EFFECTIVE
HEIGHT

WIND LOAD (PSF)

5

10

15

20

25

30

6' - 00"

1174

1036

905

780

660

545

6' - 06"

1142

978

826

683

548

419

7' - 00"

1106

915

742

582

230

7' - 06"

1065

847

654

257

8' - 00"

1019

775

500

8' - 06"

968

701

9' - 00"

913

506

9' - 06"

856

125

10' - 00"

796

10' - 06"

687

11' - 00"

460

11' - 06"

255

12' - 00"

68

  1. The maximum axial load in (pounds per linear foot of wall) is based on the short-term load duration.
  2. The lateral load deflection is limited to L/180
  3. "Empty Cells" imply no safe axial wall load for these combinations of span and wind load.

back to top



Printer Friendly Version

6 1/2" EMERCOR STRUCTURAL INSULATED PANEL (SIP)
Axial Loading (pounds/linear foot)
(OSB/OSB)

EFFECTIVE
HEIGHT

WIND LOAD (PSF)

5

10

15

20

25

30

6' - 00"

2720

2540

2365

2195

2029

1868

6' - 06"

2680

2463

2256

2056

1864

1677

7' - 00"

2633

2376

2135

1905

1686

1476

7' - 06"

2578

2279

2003

1744

1500

1268

8' - 00"

2516

2172

1861

1575

1308

1058

8' - 06"

2446

2056

1713

1402

1116

849

9' - 00"

2366

1932

1559

1227

925

76

9' - 06"

2277

1802

1404

1054

180

10' - 00"

2179

1668

1249

494

10' - 06"

2074

1532

1001

11' - 00"

1963

1397

415

11' - 06"

1849

1212

12' - 00"

1733

780

12' - 06"

1618

386

13' - 00"

1504

23

13' - 06"

1248

14' - 00"

993

14' - 06"

758

15' - 00"

541

15' - 06"

339

16' - 00"

150

  1. The maximum axial load in (pounds per linear foot of wall) is based on the short-term load duration.
  2. The lateral load deflection is limited to L/180
  3. "Empty Cells" imply no safe axial wall load for these combinations of span and wind load.

back to top



Racking Shear Capacity



Panel Type

Safe Working Load

4 1/2" OSB/Drywall

300 lbs/lin.ft.

4 1/2" OSB/OSB

400 lbs/lin.ft.



Weight of Materials



Foundation/Wall/Roof Panels

Panel Type

Panel Size

4 1/2"

6 1/2"

OSB/Drywall

129 lbs

137 1/2 lbs

OSB/OSB

127 lbs

143 lbs

OSB/PWF

-

127 lbs

*Note: Weights are based on a 4'x 8' panel

Insulated Rimboard Panels

Panel Type

Panel Size

2 7/16"

lbs/LF

lbs/Bundle

9 1/2"

4.0

640

11 7/8"

4.6

736

14"

5.2

832

16"

5.9

944

18"

6.5

1040

20"

7.2

1152

22"

7.7

1232

24"

8.2

1312

Cantilever Soffit Panels

Panel Type

Panel Size

2 1/2"

lbs/LF

Lbs/Bundle

12"

3.5

560

18"

6.0

960

24"

7.8

1248

back to top



   
 

  Copyright  |  Privacy  |  Home  |  Contact

Copyright 2005 EMERCOR Ltd. All rights Reserved.